Linear Heat Detection

combined

with Nitrogen Gas

Fire Suppression

The TW series provides the same

form of extinguishing than the

CNF series, but with a different detection form. The TW has been developed and built to detect a fire size rather than smoke, namely that heat detection.

Operating Principle

The linear heat detection cable can be easily installed through the protected volume close to the potential source of fire. The cable melts at 68ºC, or 104ºC providing fast and efficient heat/fire detection.

When dealing with very risky cabinets where heat and fire are more likely to occur than smoke development, the TW series from ExxFire offers you the fastest and most complete range of detection, as well as very quick extinguishing of the heat and/or fires created by means of a heat-sensitive cable which detects. An affordable solution with a high flexibility.

About TW systems

Linear heat detection combined with non-pressurized nitrogen fire

suppression. A system designed to protect closed server racks,

electrical cabinets and machines up to a volume of 9m3 to 27m(up to 8 interconnected systems possible).

ExxFire TW series - Overview

A system designed to early detect fire by heat and protect closed server racks, electrical cabinets, or any other enclosure up with high value equipment up to a total volume of 36m3. Explore the TW-series to find out the unit that will better meet your needs!


Integrated smoke detection and fire suppression system for small enclosures up to 1.5m3. Possible to interconnect up to 8x units for a protected total volume of 12m3.
Integrated linear heat detection and fire suppression system for small enclosures up to 3.0m3. Possible to interconnect up to 8x units for a protected total volume of 24m3.
Integrated linear heat detection and fire suppression system for small enclosures up to 4.5m3. Possible to interconnect up to 8x units for a protected total volume of 36m3.
PROTECTED VOLUME, DIMENSIONS and WEIGHT
ExxFire-TW Models
750-TW
1500-TW
2250-TW
Protected Volume

1.5m³

3.0m³

4.5m³

Footprint; Height

303x443x165mm

418x443x165 mm

580x443x165 mm

Weight

10kg (incl. 1x Cool Gas Generator)

18kg (incl. 2x Cool Gas Generators)

25kg (incl. 3x Cool Gas Generators)

OTHER SPECIFICATIONS
ExxFire-TW Models
750-TW
1500-TW
2250-TW
Output Pressure

3-5bar

3-5bar

3-5bar

Gas Mass (Volume)

0.9kg (750l)

1.8kg (1500l)

2.7kg (2250l)

Number of nitrogen Cool Gas Generators

1

2

3

For further detailed information on the TW-series, please check the following data sheet:

Do you have any questions?

Please contact us!